POP | Rack | Controller | Feed Name | AC|DC | Current AMPs | Avg AMPS (6 months) | Site Address Numbers | Suite Number | City | State | Facility Owner | Service |
ALBA | 001.001 | dwdmdcp.alba.net.internet2.edu | | DC | 25.4790 | 25.3871 | 194 | S002 | Albany | NY | Level(3) Communications | ALBA Power Circuit 60A (A+B) |
ALBA | 001.002 | sdn-dcp.alba.net.internet2.edu | | DC | 58.7466 | 58.0392 | 194 | S002 | Albany | NY | Level(3) Communications | ALBA Power Circuit 80A (A+B) |
ALBU | C01.004 | dwdmdcp.albu.net.internet2.edu | | DC | 45.0074 | 45.2672 | 505 | 112 | Albuquerque | NM | Level(3) Communications | ALBU Power Circuit 60A (A+B) |
ANL221 | Room 130D | dwdmdcp1.anl221.net.internet2.edu | | DC | 15.0104 | 15.0211 | 9700 | Building 221 | Lemont | IL | Energy Sciences Network | ANL221 Power Circuit ?A (A+B) |
ASHB | 202 | sdn-dcp.ashb.net.internet2.edu | | DC | 53.5818 | 53.5808 | 21715 | | Ashburn | VA | Equinix | ASHB Power Circuit 60A (A+B) |
ASHB | 210 | dwdmdcp.ashb.net.internet2.edu | | DC | 55.8998 | 53.1357 | 21715 | | Ashburn | VA | Equinix | ASHB Power Circuit 60A (A+B) |
ATLA | 001.001 | rtrdcp.atla.net.internet2.edu | | DC | 48.0053 | 41.1988 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit (1 of 2) 60 A (A+B) |
ATLA | 001.001 | rtrdcp2.atla.net.internet2.edu | | DC | 48.0066 | 45.0972 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit (2 of 2) 60 A (A+B) |
ATLA | 001.002 | obsacp.atla.net.internet2.edu | AA | AC | 3.8218 | 3.9689 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA AC Power Circuit 20A (120V) |
ATLA | 001.002 | obsacp.atla.net.internet2.edu | AB | AC | 5.6367 | 5.6379 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA AC Power Circuit 20A (120V) |
ATLA | 003.001 | dwdmdcp.atla.net.internet2.edu | | DC | 43.5119 | 43.6132 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
ATLA | 003.002 | dwdmdcp2.atla.net.internet2.edu | | DC | 43.4081 | 42.7775 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
ATLA | 003.003 | dwdmdcp3.atla.net.internet2.edu | | DC | 17.5948 | 15.0417 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
BALT | 001.001 | dwdmdcp.balt.net.internet2.edu | | DC | 8.9561 | 8.9446 | 300 | No Suite.
ICC | Baltimore | MD | Level(3) Communications | |
BATO | 001.001 | dwdmdcp.bato.net.internet2.edu | | DC | 25.6687 | 25.5400 | 9826 | S005 | Baton Rouge | LA | Level(3) Communications | BATO Power Circuit 60A (A+B) |
BATO | 001.002 | sdn-dcp.bato.net.internet2.edu | | DC | 49.5802 | 49.3970 | 9826 | S005 | Baton Rouge | LA | Level(3) Communications | BATO Power Circuit 60A (A+B) |
BOIS | 002.001 | dwdmdcp.bois.net.internet2.edu | | DC | 30.4114 | 30.4603 | 435 | | Boise | ID | Level(3) Communications | BOIS Power Circuit 60A (A+B) |
BOST | 001.001 | dwdmdcp.bost.net.internet2.edu | | DC | 37.4137 | 37.1701 | 300 | S002 | Boston | MA | Level(3) Communications | BOST Power Circuit 60A (A+B) |
BOST | 001.002 | sdn-dcp.bost.net.internet2.edu | | DC | 62.6243 | 62.9223 | 300 | S002 | Boston | MA | Level(3) Communications | BOST Power Circuit 80A (A+B) |
BUFF | 208.05 | dwdmdcp.buff.net.internet2.edu | | DC | 13.0729 | 12.5989 | 325 | | Buffalo | NY | Level(3) Communications | BUFF Power Circuit 60A (A+B) |
CHAR | 001.001 | dwdmdcp.char.net.internet2.edu | | DC | 41.0171 | 41.3733 | 4021 | | Charlotte | NC | Level(3) Communications | CHAR Power Circuit 60A (A+B) |
CHAR | 001.003 | sdn-dcp.char.net.internet2.edu | | DC | 51.3943 | 51.7628 | 4021 | | Charlotte | NC | Level(3) Communications | CHAR Power Circuit 80A (A+B) |
CHAT | 206.05 | dwdmdcp.chat.net.internet2.edu | | DC | 14.4464 | 14.3947 | 1601 | | Chattanooga | TN | Level(3) Communications | CHAT Power Circuit 60A (A+B) |
CHIC | 01.02 | sdn-dcp.chic.net.internet2.edu | | DC | 6.7454 | 6.8205 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.03 | dwdmdcp3.chic.net.internet2.edu | | DC | 66.5146 | 68.3853 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.04 | dwdmdcp.chic.net.internet2.edu | | DC | 39.7020 | 39.7584 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.05 | dwdmdcp2.chic.net.internet2.edu | | DC | 39.2748 | 39.3095 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 02.01 | obsacp.chic.net.internet2.edu | AA | AC | 7.0367 | 7.2204 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC AC Power Circuit 30A (120V) |
CHIC | 02.01 | obsacp.chic.net.internet2.edu | AB | AC | 5.5006 | 5.5008 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC AC Power Circuit 30A (120V) |
CHIC | 02.02 | rtrdcp.chic.net.internet2.edu | | DC | 49.7606 | 49.6942 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 02.02 | rtrdcp2.chic.net.internet2.edu | | DC | 43.1313 | 42.1569 | 600 | S012 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CINC | .01 | dwdmdcp.cinc.net.internet2.edu | | DC | 25.2858 | 23.9130 | 400 | | Cincinnati | OH | Level(3) Communications | CINC Power Circuit 60A (A+B) |
CLEV | 01.01 | dwdmdcp.clev.net.internet2.edu | | DC | 41.7665 | 41.3637 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 01.02 | dwdmdcp2.clev.net.internet2.edu | | DC | 59.9961 | 59.3639 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 01.03 | rtrdcp.clev.net.internet2.edu | | DC | 37.3539 | 44.5131 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 01.03 | rtrdcp2.clev.net.internet2.edu | | DC | 40.4875 | 36.2971 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 03.03 | dwdmdcp3.clev.net.internet2.edu | | DC | 9.5001 | 9.4716 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
DALL | 001.001 | dwdmdcp.dall.net.internet2.edu | | DC | 36.5380 | 36.6415 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 60A (A+B) |
DALL | 001.002 | sdn-dcp.dall.net.internet2.edu | | DC | 58.2584 | 53.9167 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 80A (A+B) |
DALL | 001.003 | dwdmdcp2.dall.net.internet2.edu | | DC | 18.5003 | 11.8570 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 60A (A+B) |
DENV | 001.001 | dwdmdcp.denv.net.internet2.edu | | DC | 56.6009 | 55.9538 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 75A (A+B) |
DENV | 001.002 | acp.denv.net.internet2.edu | AA | AC | 1.0939 | 1.0975 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV AC Power Circuit 20A (120v) |
DENV | 001.002 | acp.denv.net.internet2.edu | AB | AC | 0.0374 | 0.0283 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV AC Power Circuit 20A (120v) |
DENV | 001.002 | dwdmdcp2.denv.net.internet2.edu | | DC | 50.6261 | 49.3704 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 60A (A+B) |
DENV | 002.003 | sdn-dcp.denv.net.internet2.edu | | DC | 57.8543 | 57.7275 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 75A (A+B) |
DETR | C002.0000.005.005 | dwdmdcp.detr.net.internet2.edu | | DC | 12.5000 | 12.4713 | 19675 | | Detroit (Southfield) | MI | Level(3) Communications | DETR Power Circuit 60A (A+B) |
ELPA | 214.001 | dwdmdcp2.elpa.net.internet2.edu | | DC | 33.1618 | 33.5984 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 60A (A+B) |
ELPA | 214.002 | dwdmdcp.elpa.net.internet2.edu | | DC | 37.0017 | 39.4586 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 60A (A+B) |
ELPA | 232.001 | sdn-dcp0.elpa.net.internet2.edu | | DC | 50.6354 | 51.6932 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 75A (A+B) |
EQCH | 01.01 | dwdmdcp.eqch.net.internet2.edu | | DC | 33.9682 | 33.8591 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.02 | dwdmdcp2.eqch.net.internet2.edu | | DC | 37.1518 | 36.9633 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.03 | sdn-dcp.eqch.net.internet2.edu | | DC | 40.8749 | 50.2512 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.03 | sdn-dcp2.eqch.net.internet2.edu | | DC | 35.7355 | 35.6561 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EUGE | 001.007 | dwdmdcp.euge.net.internet2.edu | | DC | 37.3481 | 36.8469 | 90470 | | Eugene | OR | Level(3) Communications | EUGE Power Circuit 60A (A+B) |
FNALFCC | 1 | dwdmdcp1.fnalfcc.net.internet2.edu | | DC | 18.7999 | 18.5317 | 2 | | Batavia | IL | Energy Sciences Network | |
HART2 | C01.07 | dwdmdcp.hart2.net.internet2.edu | | DC | 20.5000 | 20.6402 | 155 | | Hartford | CT | Level(3) Communications | HART2 Power Circuit 60A (A+B) |
HART2 | C01.08 | sdn-dcp.hart2.net.internet2.edu | | DC | 37.7462 | 37.8991 | 155 | | Hartford | CT | Level(3) Communications | HART2 Power Circuit 60A (A+B) |
HOUH | 202.024 | dwdmdcp.houh.net.internet2.edu | | DC | 14.0000 | 13.9965 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 60A (A+B) |
HOUH | 202.025 | dwdmdcp2.houh.net.internet2.edu | | DC | 45.9919 | 46.0091 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 60A (A+B) |
HOUH | 202.026 | sdn-dcp.houh.net.internet2.edu | | DC | 32.0711 | 32.0689 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 80A (A+B) |
HOUS | 001.002 | dwdmdcp.hous.net.internet2.edu | | DC | 28.7620 | 30.6014 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 001.003 | dwdmdcp2.hous.net.internet2.edu | | DC | 32.5894 | 35.3294 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 001.004 | dwdmdcp3.hous.net.internet2.edu | | DC | 14.5242 | 14.3978 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.001 | rtrdcp.hous.net.internet2.edu | | DC | 21.0010 | 29.1645 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.001 | rtrdcp2.hous.net.internet2.edu | | DC | 30.5132 | 27.9849 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.002 | obsacp.hous.net.internet2.edu | AA | AC | 5.2527 | 5.2544 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS AC Power Circuit 30A (120V) |
HOUS | 003.002 | obsacp.hous.net.internet2.edu | AB | AC | 1.7500 | 1.7500 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS AC Power Circuit 30A (120V) |
INDI | 04a | dwdmdcp.indi.net.internet2.edu | | DC | 27.2437 | 23.1444 | 733 | | Indianapolis | IN | Lifeline Data Centers | INDI Power Circuit 60A (A+B) |
INDI | 06A | sdn-dcp.indi.net.internet2.edu | | DC | 50.1802 | 51.5765 | 733 | | Indianapolis | IN | Lifeline Data Centers | INDI Power Circuit 75A (A+B) |
JACK | 001.001 | dwdmdcp.jack.net.internet2.edu | | DC | 26.0173 | 25.9718 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 60A (A+B) |
JACK | 001.002 | dwdmdcp2.jack.net.internet2.edu | | DC | 5.0000 | 4.9968 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 60A (A+B) |
JACK | 001.003 | sdn-dcp3.jack.net.internet2.edu | | DC | 63.1408 | 62.9544 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 80A (A+B) |
JCSN | 001.001 | dwdmdcp.jcsn.net.internet2.edu | | DC | 24.0037 | 24.1828 | 111 | S001 | Jackson | MS | Level(3) Communications | JCSN Power Circuit 60A (A+B) |
JCSN | 001.003 | sdn-dcp.jcsn.net.internet2.edu | | DC | 44.1346 | 44.2038 | 111 | S001 | Jackson | MS | Level(3) Communications | JCSN Power Circuit 80A (A+B) |
JGI | Floor 1 / Room 422 | dwdmdcp.jgi.net.internet2.edu | | DC | 12.9996 | 13.0134 | 2800 | | Walnut Creek | CA | Energy Sciences Network | |
KANS | 003.001 | rtrdcp.kans.net.internet2.edu | | DC | 41.4411 | 41.0810 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
KANS | 003.001 | rtrdcp2.kans.net.internet2.edu | | DC | 43.4396 | 46.0413 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
KANS | 003.003 | sdn-dcp2.kans.net.internet2.edu | | DC | 0.0000 | 0.0000 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 80A (A+B) |
KANS | 004.003 | dwdmdcp.kans.net.internet2.edu | | DC | 48.6097 | 51.0881 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
LACY | 410.01 | dwdmdcp.lacy.net.internet2.edu | | DC | 9.0252 | 8.9917 | 3348 | | Lacy | WA | Level(3) Communications | LACY Power Circuit 60A (A+B) |
LASV | 001.0001.C02.005 | sdn-dcp.lasv.net.internet2.edu | | DC | 49.9143 | 49.4782 | 1 | | North Las Vegas | NV | Level(3) Communications | LASV Power Circuit 60A (A+B) |
LASV | 1.03.002 | dwdmdcp.lasv.net.internet2.edu | | DC | 26.5220 | 25.6498 | 1 | | North Las Vegas | NV | Level(3) Communications | LASV Power Circuit 60A (A+B) |
LBNL | I-8 | dwdmdcp.lbnl.net.internet2.edu | | DC | 46.6269 | 44.5776 | 1 | | Berkeley | CA | Energy Sciences Network | |
LOSA | 001.001 | rtrdcp.losa.net.internet2.edu | | DC | 44.5367 | 49.2395 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 001.001 | rtrdcp2.losa.net.internet2.edu | | DC | 50.9674 | 48.2588 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 001.002 | obsacp2.losa.net.internet2.edu | AA | AC | 10.0661 | 12.1806 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 30A (120V) |
LOSA | 001.002 | obsacp2.losa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 30A (120V) |
LOSA | 001.003 | acp.losa.net.internet2.edu | AA | AC | 7.5170 | 7.4344 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA AC Power Circuit 30A (120V) |
LOSA | 001.003 | acp.losa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA AC Power Circuit 30A (120V) |
LOSA | 002.001 | dwdmdcp.losa.net.internet2.edu | | DC | 47.7574 | 45.8364 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 002.002 | dwdmdcp2.losa.net.internet2.edu | | DC | 27.4053 | 27.4223 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOUI | 001.001 | dwdmdcp.loui.net.internet2.edu | | DC | 22.1807 | 22.2421 | 848 | | Louisville | KY | Level(3) Communications | LOUI Power Circuit 60A (A+B) |
LOUI | 001.003 | sdn-dcp.loui.net.internet2.edu | | DC | 53.5414 | 52.0448 | 848 | | Louisville | KY | Level(3) Communications | LOUI Power Circuit 70A (A+B) |
MEMP | C03.011 | dwdmdcp.memp.net.internet2.edu | | DC | 20.6294 | 20.5389 | 3993 | | Memphis | TN | Level(3) Communications | MEMP Power Circuit 60A (A+B) |
MINN | 001.003 | sdn-dcp.minn.net.internet2.edu | | DC | 28.9332 | 38.9666 | 511 | | Minneapolis | MN | University of Minnesota - Twin Cities | MINN Power Circuit 70A (A+B) |
MINN | 001.003 | sdn-dcp2.minn.net.internet2.edu | | DC | 31.4864 | 31.5194 | 511 | | Minneapolis | MN | University of Minnesota - Twin Cities | MINN Power Circuit 70A (A+B) |
MISS2 | 503.101.11 | sdn-dcp.miss2.net.internet2.edu | | DC | 50.3106 | 50.6601 | 110 | 503 | Missoula | MT | iConnect Montana | |
NASH | 001.001 | dwdmdcp.nash.net.internet2.edu | | DC | 35.4300 | 35.3124 | 2990 | S009 | Nashville | TN | Level(3) Communications | NASH Power Circuit 60A (A+B) |
NASH | 001.002 | dwdmdcp2.nash.net.internet2.edu | | DC | 33.6496 | 33.6996 | 2990 | S009 | Nashville | TN | Level(3) Communications | NASH Power Circuit 60A (A+B) |
NERSC | 01 | dwdmdcp.nersc.net.internet2.edu | | DC | 30.8020 | 30.8089 | 415 | | Oakland | CA | Energy Sciences Network | |
NEWY1118TH | 001.003 | obsacp.newy1118th.net.internet2.edu | AA | AC | 0.2529 | 0.2537 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 AC Power Circuit 20A (120V) |
NEWY1118TH | 001.003 | obsacp.newy1118th.net.internet2.edu | AB | AC | 1.0000 | 0.9987 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 AC Power Circuit 20A (120V) |
NEWY1118TH | 001.004 | dwdmdcp2.newy1118th.net.internet2.edu | | DC | 37.3099 | 35.7896 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 Power Circuit 50A (A+B) |
NEWY1118TH | 001.005 | dwdmdcp.newy1118th.net.internet2.edu | | DC | 24.6270 | 27.6663 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 Power Circuit 60A (A+B) |
NEWY32AOA | 06.07 | obsacp.newy32aoa.net.internet2.edu | AA | AC | 16.8019 | 14.9403 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit AC (TBD) |
NEWY32AOA | 06.07 | obsacp.newy32aoa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit AC (TBD) |
NEWY32AOA | 06.08 | rtrdcp.newy32aoa.net.internet2.edu | | DC | 49.8836 | 46.4141 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 50A (A+B) |
NEWY32AOA | 06.08 | rtrdcp2.newy32aoa.net.internet2.edu | | DC | 40.7094 | 39.3486 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 50A (A+B) |
NEWY32AOA | 06.09 | dwdmdcp2.newy32aoa.net.internet2.edu | | DC | 37.1613 | 38.0582 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 60A (A+B) |
PAIX | 0401 | rtrdcp.paix.net.internet2.edu | | DC | 33.0936 | 32.6674 | 529 | | Palo Alto | CA | Equinix | PAIX Power Circuit 60 (A+B) |
PHIL | 001.001 | dwdmdcp.phil.net.internet2.edu | | DC | 26.3910 | 26.2448 | 401 | S010 | Philadelphia | PA | Level(3) Communications | PHIL Power Circuit 60A (A+B) |
PHIL | 001.003 | sdn-dcp.phil.net.internet2.edu | | DC | 56.8032 | 55.4628 | 401 | S010 | Philadelphia | PA | Level(3) Communications | PHIL Power Circuit 80A (A+B) |
PHOE | C001.0103.001.030 | sdn-dcp.phoe.net.internet2.edu | | DC | 54.8911 | 52.5783 | 811 | | Phoenix | AZ | Level(3) Communications | PHOE Power Circuit 80A (A+B) |
PHOE | C001.0103.001.031 | dwdmdcp.phoe.net.internet2.edu | | DC | 39.0553 | 37.0633 | 811 | | Phoenix | AZ | Level(3) Communications | PHOE Power Circuit 80A (A+B) |
PITT | 001.001 | dwdmdcp.pitt.net.internet2.edu | | DC | 28.1156 | 28.0376 | 143 | S013 | Pittsburgh | PA | Level(3) Communications | PITT Power Circuit 60A (A+B) |
PITT | 001.003 | sdn-dcp.pitt.net.internet2.edu | | DC | 58.5885 | 58.2258 | 143 | S013 | Pittsburgh | PA | Level(3) Communications | PITT Power Circuit 80A (A+B) |
PORT | 001.001 | dwdmdcp.port.net.internet2.edu | | DC | 25.5652 | 25.6358 | 1335 | 011 | Portland | OR | Level(3) Communications | PORT Power Circuit 60A (A+B) |
PORT | 001.004 | sdn-dcp.port.net.internet2.edu | | DC | 64.5069 | 64.3703 | 1335 | 011 | Portland | OR | Level(3) Communications | PORT Power Circuit 80A (A+B) |
PUEB | 2.02 | dwdmdcp.pueb.net.internet2.edu | | DC | 17.5738 | 17.7016 | 211 | | Pueblo | CO | CenturyLink | |
RALE | 001.001 | dwdmdcp.rale.net.internet2.edu | | DC | 30.0000 | 29.9834 | 5301 | Dark Fiber - S007 | Raleigh | NC | Level(3) Communications | RALE Power Circuit 60 A (A+B) |
RALE | 001.003 | sdn-dcp.rale.net.internet2.edu | | DC | 60.4476 | 60.6517 | 5301 | Dark Fiber - S007 | Raleigh | NC | Level(3) Communications | RALE Power Circuit 80A (A+B) |
RENO | 210.05 | dwdmdcp.reno.net.internet2.edu | | DC | 16.5620 | 16.6087 | 220 | | Reno | NV | Level(3) Communications | RENO Power Circuit 60A (A+B) |
RENO | 216.002 | sdn-dcp.reno.net.internet2.edu | | DC | 51.9105 | 51.7215 | 220 | | Reno | NV | Level(3) Communications | RENO Power Circuit 80A (A+B) |
SACR | 001.001 | dwdmdcp.sacr.net.internet2.edu | | DC | 23.1347 | 22.9532 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SACR | 001.002 | dwdmdcp2.sacr.net.internet2.edu | | DC | 17.0447 | 15.3284 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SACR | 001.003 | dwdmdcp3.sacr.net.internet2.edu | | DC | 6.0000 | 5.9972 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SAIN | 210.002 | dwdmdcp.sain.net.internet2.edu | | DC | 11.1502 | 12.2622 | 900 | | Saint Louis | MO | Level(3) Communications | SAIN Power Circuit 60A (A+B) |
SALT | 001.001 | rtrdcp.salt.net.internet2.edu | | DC | 38.3534 | 34.5771 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.001 | rtrdcp2.salt.net.internet2.edu | | DC | 31.9079 | 37.7488 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.002 | obsacp.salt.net.internet2.edu | AA | AC | 10.0056 | 9.9615 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.002 | obsacp.salt.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.003 | dwdmdcp.salt.net.internet2.edu | | DC | 49.5331 | 49.0815 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.004 | dwdmdcp2.salt.net.internet2.edu | | DC | 29.6956 | 29.8047 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SANA | 202.010 | dwdmdcp.sana.net.internet2.edu | | DC | 10.5000 | 10.5637 | 1203 | | San Antonio | TX | Level(3) Communications | SANA Power Circuit 60A (A+B) |
SAND | 1.003 | dwdmdcp.sand.net.internet2.edu | | DC | 8.0000 | 7.9948 | 8929 | S014 | San Diego | CA | Level(3) Communications | SAND Power Circuit 60A (A+B) |
SANL | LT01.09 cabinet rack | dwdmdcp.sanl.net.internet2.edu | | DC | 20.4723 | 20.5248 | 775 | | San Luis Obispo | CA | Level(3) Communications | SANL Power Circuit 60A (A+B) |
SEAT | 03.04 | rtrdcp.seat.net.internet2.edu | | DC | 34.7984 | 34.4253 | 2001 | 803 | Seattle | WA | Pacific Northwest Gigapop | SEAT (Westin) Power Circuit (#1 of 2) 100A (A+B) |
SEAT | 03.04 | rtrdcp2.seat.net.internet2.edu | | DC | 43.0229 | 40.0003 | 2001 | 803 | Seattle | WA | Pacific Northwest Gigapop | SEAT (Westin) Power Circuit (#2 of 2) 100A (A+B) |
SLAC | 1 | dwdmdcp.slac.net.internet2.edu | | DC | 17.3163 | 17.2781 | 2575 | | Stanford | CA | Energy Sciences Network | |
STAR | 0205.07 | sdn-dcp0.star.net.internet2.edu | | DC | 40.4191 | 52.3082 | 710 | 600 | Chicago | IL | Starlight Northwestern University | STAR Power Circuit 100A (A+B) |
STAR | 0205.08 | dwdmdcp.star.net.internet2.edu | | DC | 46.0046 | 46.0349 | 710 | 600 | Chicago | IL | Starlight Northwestern University | STAR Power Circuit 60A (A+B) |
SUNN | 001.001 | dwdmdcp2.sunn.net.internet2.edu | | DC | 29.5000 | 29.4943 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 60A (A+B) |
SUNN | 001.002 | dwdmdcp.sunn.net.internet2.edu | | DC | 28.7499 | 28.9184 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 60A (A+B) |
SUNN | 001.002 | obsacp.sunn.net.internet2.edu | AA | AC | 1.4712 | 1.4719 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN AC Power Circuit 20A (120V) |
SUNN | 001.002 | obsacp.sunn.net.internet2.edu | AB | AC | 0.0703 | 0.0642 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN AC Power Circuit 20A (120V) |
SUNN | 001.003 | dwdmdcp3.sunn.net.internet2.edu | | DC | 44.7341 | 35.8660 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 80A (A+B) |
SUNN | 001.004 | sdn-dcp0.sunn.net.internet2.edu | | DC | 36.0744 | 55.3691 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit (#1 of 2) 60A (A+B) |
SUNN | 001.004 | sdn-dcp2.sunn.net.internet2.edu | | DC | 34.8564 | 35.3541 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit (#2 of 2) 60A (A+B) |
Sing1 | 43c125 | acp.sing1.net.internet2.edu | AA | AC | 0.3070 | 2.2217 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c125 | acp.sing1.net.internet2.edu | AB | AC | 0.3033 | 2.1984 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c126 | acp0.sing1.net.internet2.edu | AA | AC | 3.8217 | 2.2054 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c126 | acp0.sing1.net.internet2.edu | AB | AC | 4.0750 | 2.3574 | 35 | Internet2 | Singapore | | TATA Communications | |
TUCS | 204.004 | dwdmdcp.tucs.net.internet2.edu | | DC | 24.3723 | 23.5531 | 135 | S002 | Tucson | AZ | Level(3) Communications | |
TUCS | 204.005 | sdn-dcp.tucs.net.internet2.edu | | DC | 52.5027 | 51.5680 | 135 | S002 | Tucson | AZ | Level(3) Communications | TUCS Power Circuit 80A (A+B) |
TULS | C001.0000.204.007 | dwdmdcp2.tuls.net.internet2.edu | | DC | 21.1994 | 21.2866 | 18 | | Tulsa | OK | Level(3) Communications | TULS Power Circuit 60A (A+B) |
TULS | C001.0000.204.008 | sdn-dcp.tuls.net.internet2.edu | | DC | 52.8363 | 53.6809 | 18 | | Tulsa | OK | Level(3) Communications | TULS Power Circuit 80A (A+B) |
WASH | 001.002 | obsacp.wash.net.internet2.edu | AA | AC | 3.4987 | 3.5447 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 30A (A+B) 120V |
WASH | 001.002 | obsacp.wash.net.internet2.edu | AB | AC | 3.5005 | 3.5428 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 30A (A+B) 120V |
WASH | 001.002 | rtrdcp.wash.net.internet2.edu | | DC | 42.3273 | 39.6472 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.002 | rtrdcp2.wash.net.internet2.edu | | DC | 42.9384 | 40.4314 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.003 | obsacp2.wash.net.internet2.edu | AA | AC | 2.0011 | 2.0009 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 20A (A+B) 120V |
WASH | 001.003 | obsacp2.wash.net.internet2.edu | AB | AC | 2.5000 | 2.5000 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 20A (A+B) 120V |
WASH | 001.004 | dwdmdcp2.wash.net.internet2.edu | | DC | 51.5950 | 49.0495 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.005 | dwdmdcp.wash.net.internet2.edu | | DC | 45.8570 | 45.1149 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 002.003 | sdn-dcp.wash.net.internet2.edu | | DC | 0.0000 | 0.0000 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 002.003 | sdn-dcp2.wash.net.internet2.edu | | DC | 0.0000 | 0.0000 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 002.005 | dwdmdcp3.wash.net.internet2.edu | | DC | 51.0731 | 40.4464 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH2 | 001.002 | obsacp.net.wix.internet2.edu | AA | AC | 0.0000 | 0.0000 | 1755 | | McLean | VA | Level(3) Communications | |
WASH2 | 001.002 | obsacp.net.wix.internet2.edu | AB | AC | 0.0000 | 0.0000 | 1755 | | McLean | VA | Level(3) Communications | |
WILC | Rack 2 | rtrdcp.wilc.net.internet2.edu | | DC | 37.1925 | 37.2314 | 624 | | Los Angeles | CA | Wilcon | WILC Power Circuit 60A (A+B) |
|