POP | Rack | Controller | Feed Name | AC|DC | Current AMPs | Avg AMPS (6 months) | Site Address Numbers | Suite Number | City | State | Facility Owner | Service |
ALBA | 001.001 | dwdmdcp.alba.net.internet2.edu | | DC | 21.3649 | 25.3767 | 194 | S002 | Albany | NY | Level(3) Communications | ALBA Power Circuit 60A (A+B) |
ALBA | 001.002 | sdn-dcp.alba.net.internet2.edu | | DC | 57.0300 | 57.7729 | 194 | S002 | Albany | NY | Level(3) Communications | ALBA Power Circuit 80A (A+B) |
ALBU | C01.004 | dwdmdcp.albu.net.internet2.edu | | DC | 45.3432 | 45.0085 | 505 | 112 | Albuquerque | NM | Level(3) Communications | ALBU Power Circuit 60A (A+B) |
ANL221 | Room 130D | dwdmdcp1.anl221.net.internet2.edu | | DC | 15.0177 | 14.9486 | 9700 | Building 221 | Lemont | IL | Energy Sciences Network | ANL221 Power Circuit ?A (A+B) |
ASHB | 202 | sdn-dcp.ashb.net.internet2.edu | | DC | 53.8231 | 53.5824 | 21715 | | Ashburn | VA | Equinix | ASHB Power Circuit 60A (A+B) |
ASHB | 210 | dwdmdcp.ashb.net.internet2.edu | | DC | 36.8399 | 47.0704 | 21715 | | Ashburn | VA | Equinix | ASHB Power Circuit 80A (A+B) |
ATLA | 001.001 | rtrdcp.atla.net.internet2.edu | | DC | 45.6376 | 46.1601 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit (1 of 2) 60 A (A+B) |
ATLA | 001.001 | rtrdcp2.atla.net.internet2.edu | | DC | 44.6978 | 45.3652 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit (2 of 2) 60 A (A+B) |
ATLA | 001.002 | obsacp.atla.net.internet2.edu | AA | AC | 3.7733 | 3.8570 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA AC Power Circuit 20A (120V) |
ATLA | 001.002 | obsacp.atla.net.internet2.edu | AB | AC | 5.6598 | 5.6645 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA AC Power Circuit 20A (120V) |
ATLA | 003.001 | dwdmdcp.atla.net.internet2.edu | | DC | 42.8594 | 43.5921 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
ATLA | 003.002 | dwdmdcp2.atla.net.internet2.edu | | DC | 42.6520 | 43.2799 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
ATLA | 003.003 | dwdmdcp3.atla.net.internet2.edu | | DC | 17.5907 | 17.8327 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
BALT | 001.001 | dwdmdcp.balt.net.internet2.edu | | DC | 7.2905 | 8.8720 | 300 | No Suite.
ICC | Baltimore | MD | Level(3) Communications | |
BATO | 001.001 | dwdmdcp.bato.net.internet2.edu | | DC | 25.5231 | 25.6353 | 9826 | S005 | Baton Rouge | LA | Level(3) Communications | BATO Power Circuit 60A (A+B) |
BATO | 001.002 | sdn-dcp.bato.net.internet2.edu | | DC | 49.4433 | 49.7466 | 9826 | S005 | Baton Rouge | LA | Level(3) Communications | BATO Power Circuit 60A (A+B) |
BOIS | 002.001 | dwdmdcp.bois.net.internet2.edu | | DC | 30.5617 | 30.8636 | 435 | | Boise | ID | Level(3) Communications | BOIS Power Circuit 60A (A+B) |
BOST | 001.001 | dwdmdcp.bost.net.internet2.edu | | DC | 31.5052 | 37.1590 | 300 | S002 | Boston | MA | Level(3) Communications | BOST Power Circuit 60A (A+B) |
BOST | 001.002 | sdn-dcp.bost.net.internet2.edu | | DC | 62.4246 | 62.5470 | 300 | S002 | Boston | MA | Level(3) Communications | BOST Power Circuit 80A (A+B) |
BUFF | 208.05 | dwdmdcp.buff.net.internet2.edu | | DC | 10.4855 | 12.8575 | 325 | | Buffalo | NY | Level(3) Communications | BUFF Power Circuit 60A (A+B) |
CHAR | 001.001 | dwdmdcp.char.net.internet2.edu | | DC | 40.9642 | 40.8952 | 4021 | | Charlotte | NC | Level(3) Communications | CHAR Power Circuit 60A (A+B) |
CHAR | 001.003 | sdn-dcp.char.net.internet2.edu | | DC | 50.7756 | 51.1955 | 4021 | | Charlotte | NC | Level(3) Communications | CHAR Power Circuit 80A (A+B) |
CHAT | 206.05 | dwdmdcp.chat.net.internet2.edu | | DC | 14.1277 | 14.5365 | 1601 | | Chattanooga | TN | Level(3) Communications | CHAT Power Circuit 60A (A+B) |
CHIC | 01.02 | sdn-dcp.chic.net.internet2.edu | | DC | 6.5484 | 6.6484 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.03 | dwdmdcp3.chic.net.internet2.edu | | DC | 67.5496 | 67.3312 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.04 | dwdmdcp.chic.net.internet2.edu | | DC | 39.9159 | 39.9663 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.05 | dwdmdcp2.chic.net.internet2.edu | | DC | 39.7293 | 39.4991 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 02.01 | obsacp.chic.net.internet2.edu | AA | AC | 7.0288 | 7.0320 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC AC Power Circuit 30A (120V) |
CHIC | 02.01 | obsacp.chic.net.internet2.edu | AB | AC | 5.5009 | 5.5007 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC AC Power Circuit 30A (120V) |
CHIC | 02.02 | rtrdcp.chic.net.internet2.edu | | DC | 39.9799 | 48.2436 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 02.02 | rtrdcp2.chic.net.internet2.edu | | DC | 43.9662 | 43.5659 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CINC | .01 | dwdmdcp.cinc.net.internet2.edu | | DC | 25.0074 | 24.9301 | 400 | | Cincinnati | OH | Level(3) Communications | CINC Power Circuit 60A (A+B) |
CLEV | 01.01 | dwdmdcp.clev.net.internet2.edu | | DC | 35.0697 | 41.6284 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 01.02 | dwdmdcp2.clev.net.internet2.edu | | DC | 50.3426 | 59.7748 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 75A (A+B) |
CLEV | 01.03 | rtrdcp.clev.net.internet2.edu | | DC | 39.1300 | 37.6511 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 01.03 | rtrdcp2.clev.net.internet2.edu | | DC | 42.4979 | 40.6662 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 03.03 | dwdmdcp3.clev.net.internet2.edu | | DC | 17.1363 | 11.9680 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
DALL | 001.001 | dwdmdcp.dall.net.internet2.edu | | DC | 40.8587 | 36.9566 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 60A (A+B) |
DALL | 001.002 | sdn-dcp.dall.net.internet2.edu | | DC | 74.4463 | 59.4315 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 80A (A+B) |
DALL | 001.003 | dwdmdcp2.dall.net.internet2.edu | | DC | 19.4325 | 18.7227 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 60A (A+B) |
DENV | 001.001 | dwdmdcp.denv.net.internet2.edu | | DC | 56.6650 | 56.1433 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 75A (A+B) |
DENV | 001.002 | acp.denv.net.internet2.edu | AA | AC | 1.2636 | 1.1627 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV AC Power Circuit 20A (120v) |
DENV | 001.002 | acp.denv.net.internet2.edu | AB | AC | 0.0254 | 0.0347 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV AC Power Circuit 20A (120v) |
DENV | 001.002 | dwdmdcp2.denv.net.internet2.edu | | DC | 50.2670 | 50.6466 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 80A (A+B) |
DENV | 002.003 | sdn-dcp.denv.net.internet2.edu | | DC | 57.9788 | 59.0518 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 80A (A+B) |
DETR | C002.0000.005.005 | dwdmdcp.detr.net.internet2.edu | | DC | 12.4365 | 12.5060 | 19675 | | Detroit (Southfield) | MI | Level(3) Communications | DETR Power Circuit 60A (A+B) |
ELPA | 214.001 | dwdmdcp2.elpa.net.internet2.edu | | DC | 33.2981 | 33.1139 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 60A (A+B) |
ELPA | 214.002 | dwdmdcp.elpa.net.internet2.edu | | DC | 37.1081 | 37.0252 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 60A (A+B) |
ELPA | 232.001 | sdn-dcp0.elpa.net.internet2.edu | | DC | 51.6968 | 50.6577 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 75A (A+B) |
EQCH | 01.01 | dwdmdcp.eqch.net.internet2.edu | | DC | 33.9255 | 33.9504 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.02 | dwdmdcp2.eqch.net.internet2.edu | | DC | 38.1419 | 37.6283 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.03 | sdn-dcp.eqch.net.internet2.edu | | DC | 39.3160 | 41.6930 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.03 | sdn-dcp2.eqch.net.internet2.edu | | DC | 34.1628 | 36.1860 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EUGE | 001.007 | dwdmdcp.euge.net.internet2.edu | | DC | 37.1338 | 37.1961 | 90470 | | Eugene | OR | Level(3) Communications | EUGE Power Circuit 60A (A+B) |
FNALFCC | 1 | dwdmdcp1.fnalfcc.net.internet2.edu | | DC | 18.8204 | 18.6302 | 2 | | Batavia | IL | Energy Sciences Network | |
HART2 | C01.07 | dwdmdcp.hart2.net.internet2.edu | | DC | 18.2140 | 20.7207 | 155 | | Hartford | CT | Level(3) Communications | HART2 Power Circuit 60A (A+B) |
HART2 | C01.08 | sdn-dcp.hart2.net.internet2.edu | | DC | 38.1609 | 37.8185 | 155 | | Hartford | CT | Level(3) Communications | HART2 Power Circuit 60A (A+B) |
HOUH | 202.024 | dwdmdcp.houh.net.internet2.edu | | DC | 14.0038 | 13.9888 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 60A (A+B) |
HOUH | 202.025 | dwdmdcp2.houh.net.internet2.edu | | DC | 46.2502 | 46.0486 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 60A (A+B) |
HOUH | 202.026 | sdn-dcp.houh.net.internet2.edu | | DC | 61.0221 | 60.9919 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 80A (A+B) |
HOUS | 001.002 | dwdmdcp.hous.net.internet2.edu | | DC | 28.7408 | 28.6829 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 001.003 | dwdmdcp2.hous.net.internet2.edu | | DC | 33.0000 | 32.8615 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 001.004 | dwdmdcp3.hous.net.internet2.edu | | DC | 14.2995 | 14.3625 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.001 | rtrdcp.hous.net.internet2.edu | | DC | 21.0002 | 21.2633 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.001 | rtrdcp2.hous.net.internet2.edu | | DC | 30.6653 | 30.6321 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.002 | obsacp.hous.net.internet2.edu | AA | AC | 5.2507 | 5.2503 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS AC Power Circuit 30A (120V) |
HOUS | 003.002 | obsacp.hous.net.internet2.edu | AB | AC | 1.7500 | 1.7496 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS AC Power Circuit 30A (120V) |
INDI | 04a | dwdmdcp.indi.net.internet2.edu | | DC | 27.1968 | 27.4871 | 733 | | Indianapolis | IN | Lifeline Data Centers | INDI Power Circuit 60A (A+B) |
INDI | 06A | sdn-dcp.indi.net.internet2.edu | | DC | 57.0723 | 52.8954 | 733 | | Indianapolis | IN | Lifeline Data Centers | INDI Power Circuit 75A (A+B) |
JACK | 001.001 | dwdmdcp.jack.net.internet2.edu | | DC | 26.0592 | 25.9846 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 60A (A+B) |
JACK | 001.002 | dwdmdcp2.jack.net.internet2.edu | | DC | 5.0000 | 4.9945 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 60A (A+B) |
JACK | 001.003 | sdn-dcp3.jack.net.internet2.edu | | DC | 62.9705 | 62.7464 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 80A (A+B) |
JCSN | 001.001 | dwdmdcp.jcsn.net.internet2.edu | | DC | 24.0044 | 23.9967 | 111 | S001 | Jackson | MS | Level(3) Communications | JCSN Power Circuit 60A (A+B) |
JCSN | 001.003 | sdn-dcp.jcsn.net.internet2.edu | | DC | 43.8708 | 44.0380 | 111 | S001 | Jackson | MS | Level(3) Communications | JCSN Power Circuit 80A (A+B) |
JGI | Floor 1 / Room 422 | dwdmdcp.jgi.net.internet2.edu | | DC | 13.0812 | 12.9266 | 2800 | | Walnut Creek | CA | Energy Sciences Network | |
KANS | 003.001 | rtrdcp.kans.net.internet2.edu | | DC | 42.6028 | 41.8427 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
KANS | 003.001 | rtrdcp2.kans.net.internet2.edu | | DC | 42.5238 | 42.4917 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
KANS | 004.003 | dwdmdcp.kans.net.internet2.edu | | DC | 55.3239 | 50.2606 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 80A (A+B) |
KANS | 004.004 | dwdmdcp2.kans.net.internet2.edu | | DC | 43.2558 | 39.8461 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
LACY | 410.01 | dwdmdcp.lacy.net.internet2.edu | | DC | 8.5355 | 8.9847 | 3348 | | Lacy | WA | Level(3) Communications | LACY Power Circuit 60A (A+B) |
LASV | 001.0001.C02.005 | sdn-dcp.lasv.net.internet2.edu | | DC | 49.3387 | 49.5468 | 1 | | North Las Vegas | NV | Level(3) Communications | LASV Power Circuit 60A (A+B) |
LASV | 1.03.002 | dwdmdcp.lasv.net.internet2.edu | | DC | 26.4150 | 26.4114 | 1 | | North Las Vegas | NV | Level(3) Communications | LASV Power Circuit 60A (A+B) |
LBNL | I-8 | dwdmdcp.lbnl.net.internet2.edu | | DC | 46.3817 | 46.8232 | 1 | | Berkeley | CA | Energy Sciences Network | |
LOSA | 001.001 | rtrdcp.losa.net.internet2.edu | | DC | 39.9790 | 42.3356 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 001.001 | rtrdcp2.losa.net.internet2.edu | | DC | 47.4027 | 49.9037 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 001.002 | obsacp2.losa.net.internet2.edu | AA | AC | 10.2549 | 10.1750 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 30A (120V) |
LOSA | 001.002 | obsacp2.losa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 30A (120V) |
LOSA | 001.003 | acp.losa.net.internet2.edu | AA | AC | 5.2570 | 6.4497 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA AC Power Circuit 30A (120V) |
LOSA | 001.003 | acp.losa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA AC Power Circuit 30A (120V) |
LOSA | 002.001 | dwdmdcp.losa.net.internet2.edu | | DC | 48.7150 | 48.0541 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 002.002 | dwdmdcp2.losa.net.internet2.edu | | DC | 31.0459 | 28.7147 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOUI | 001.001 | dwdmdcp.loui.net.internet2.edu | | DC | 22.2098 | 22.2607 | 848 | | Louisville | KY | Level(3) Communications | LOUI Power Circuit 60A (A+B) |
LOUI | 001.003 | sdn-dcp.loui.net.internet2.edu | | DC | 50.6751 | 52.5984 | 848 | | Louisville | KY | Level(3) Communications | LOUI Power Circuit 70A (A+B) |
MEMP | C03.011 | dwdmdcp.memp.net.internet2.edu | | DC | 21.0103 | 20.8483 | 3993 | | Memphis | TN | Level(3) Communications | MEMP Power Circuit 60A (A+B) |
MINN | 001.003 | sdn-dcp.minn.net.internet2.edu | | DC | 28.9232 | 29.0039 | 511 | | Minneapolis | MN | University of Minnesota - Twin Cities | MINN Power Circuit 70A (A+B) |
MINN | 001.003 | sdn-dcp2.minn.net.internet2.edu | | DC | 31.8339 | 31.8329 | 511 | | Minneapolis | MN | University of Minnesota - Twin Cities | MINN Power Circuit 70A (A+B) |
MISS2 | 503.101.11 | sdn-dcp.miss2.net.internet2.edu | | DC | 52.1021 | 51.0848 | 110 | 503 | Missoula | MT | iConnect Montana | |
NASH | 001.001 | dwdmdcp.nash.net.internet2.edu | | DC | 35.4061 | 35.3908 | 2990 | S009 | Nashville | TN | Level(3) Communications | NASH Power Circuit 60A (A+B) |
NASH | 001.002 | dwdmdcp2.nash.net.internet2.edu | | DC | 33.5736 | 33.5749 | 2990 | S009 | Nashville | TN | Level(3) Communications | NASH Power Circuit 60A (A+B) |
NERSC | 01 | dwdmdcp.nersc.net.internet2.edu | | DC | 30.4809 | 30.6347 | 415 | | Oakland | CA | Energy Sciences Network | |
NEWY1118TH | 001.003 | obsacp.newy1118th.net.internet2.edu | AA | AC | 0.2529 | 0.2515 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 AC Power Circuit 20A (120V) |
NEWY1118TH | 001.003 | obsacp.newy1118th.net.internet2.edu | AB | AC | 1.0000 | 0.9943 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 AC Power Circuit 20A (120V) |
NEWY1118TH | 001.004 | dwdmdcp2.newy1118th.net.internet2.edu | | DC | 31.2129 | 37.0760 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 Power Circuit 50A (A+B) |
NEWY1118TH | 001.005 | dwdmdcp.newy1118th.net.internet2.edu | | DC | 10.9238 | 20.4781 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 Power Circuit 60A (A+B) |
NEWY32AOA | 06.07 | obsacp.newy32aoa.net.internet2.edu | AA | AC | 16.8749 | 16.8692 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit AC (TBD) |
NEWY32AOA | 06.07 | obsacp.newy32aoa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit AC (TBD) |
NEWY32AOA | 06.08 | rtrdcp.newy32aoa.net.internet2.edu | | DC | 50.0777 | 49.9897 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 60A (A+B) |
NEWY32AOA | 06.08 | rtrdcp2.newy32aoa.net.internet2.edu | | DC | 41.2302 | 40.8477 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 60A (A+B) |
NEWY32AOA | 06.09 | dwdmdcp2.newy32aoa.net.internet2.edu | | DC | 35.0823 | 39.7359 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 60A (A+B) |
PAIX | 0401 | rtrdcp.paix.net.internet2.edu | | DC | 30.6279 | 31.6579 | 529 | | Palo Alto | CA | Equinix | PAIX Power Circuit 60 (A+B) |
PHIL | 001.001 | dwdmdcp.phil.net.internet2.edu | | DC | 22.0956 | 26.3473 | 401 | S010 | Philadelphia | PA | Level(3) Communications | PHIL Power Circuit 60A (A+B) |
PHIL | 001.003 | sdn-dcp.phil.net.internet2.edu | | DC | 54.7328 | 56.0164 | 401 | S010 | Philadelphia | PA | Level(3) Communications | PHIL Power Circuit 80A (A+B) |
PHOE | C001.0103.001.030 | sdn-dcp.phoe.net.internet2.edu | | DC | 53.3051 | 53.4107 | 811 | | Phoenix | AZ | Level(3) Communications | PHOE Power Circuit 80A (A+B) |
PHOE | C001.0103.001.031 | dwdmdcp.phoe.net.internet2.edu | | DC | 38.4980 | 38.3041 | 811 | | Phoenix | AZ | Level(3) Communications | PHOE Power Circuit 80A (A+B) |
PITT | 001.001 | dwdmdcp.pitt.net.internet2.edu | | DC | 23.3394 | 27.6287 | 143 | S013 | Pittsburgh | PA | Level(3) Communications | PITT Power Circuit 60A (A+B) |
PITT | 001.003 | sdn-dcp.pitt.net.internet2.edu | | DC | 58.0992 | 57.8606 | 143 | S013 | Pittsburgh | PA | Level(3) Communications | PITT Power Circuit 80A (A+B) |
PORT | 001.001 | dwdmdcp.port.net.internet2.edu | | DC | 25.5122 | 25.4950 | 1335 | 011 | Portland | OR | Level(3) Communications | PORT Power Circuit 60A (A+B) |
PORT | 001.004 | sdn-dcp.port.net.internet2.edu | | DC | 63.9547 | 64.2387 | 1335 | 011 | Portland | OR | Level(3) Communications | PORT Power Circuit 80A (A+B) |
PUEB | 2.02 | dwdmdcp.pueb.net.internet2.edu | | DC | 17.8961 | 17.7286 | 211 | | Pueblo | CO | CenturyLink | |
RALE | 001.001 | dwdmdcp.rale.net.internet2.edu | | DC | 30.0002 | 29.9635 | 5301 | Dark Fiber - S007 | Raleigh | NC | Level(3) Communications | RALE Power Circuit 60 A (A+B) |
RALE | 001.003 | sdn-dcp.rale.net.internet2.edu | | DC | 60.3459 | 60.5107 | 5301 | Dark Fiber - S007 | Raleigh | NC | Level(3) Communications | RALE Power Circuit 80A (A+B) |
RENO | 210.05 | dwdmdcp.reno.net.internet2.edu | | DC | 17.2716 | 17.0195 | 220 | | Reno | NV | Level(3) Communications | RENO Power Circuit 60A (A+B) |
RENO | 216.002 | sdn-dcp.reno.net.internet2.edu | | DC | 52.5913 | 52.4574 | 220 | | Reno | NV | Level(3) Communications | RENO Power Circuit 80A (A+B) |
SACR | 001.001 | dwdmdcp.sacr.net.internet2.edu | | DC | 23.2503 | 23.1148 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SACR | 001.002 | dwdmdcp2.sacr.net.internet2.edu | | DC | 17.3243 | 17.1414 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SACR | 001.003 | dwdmdcp3.sacr.net.internet2.edu | | DC | 5.9999 | 5.9958 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SAIN | 210.002 | dwdmdcp.sain.net.internet2.edu | | DC | 11.0794 | 11.1969 | 900 | | Saint Louis | MO | Level(3) Communications | SAIN Power Circuit 60A (A+B) |
SALT | 001.001 | rtrdcp.salt.net.internet2.edu | | DC | 37.5585 | 36.8883 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.001 | rtrdcp2.salt.net.internet2.edu | | DC | 29.7464 | 29.9667 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.002 | obsacp.salt.net.internet2.edu | AA | AC | 9.9662 | 9.9822 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.002 | obsacp.salt.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.003 | dwdmdcp.salt.net.internet2.edu | | DC | 53.7437 | 49.1927 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 75A (A+B) |
SALT | 001.004 | dwdmdcp2.salt.net.internet2.edu | | DC | 33.2344 | 30.1560 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SANA | 202.010 | dwdmdcp.sana.net.internet2.edu | | DC | 10.5000 | 10.4909 | 1203 | | San Antonio | TX | Level(3) Communications | SANA Power Circuit 60A (A+B) |
SAND | 1.003 | dwdmdcp.sand.net.internet2.edu | | DC | 8.0000 | 7.9893 | 8929 | S014 | San Diego | CA | Level(3) Communications | SAND Power Circuit 60A (A+B) |
SANL | LT01.09 cabinet rack | dwdmdcp.sanl.net.internet2.edu | | DC | 20.7054 | 20.5446 | 775 | | San Luis Obispo | CA | Level(3) Communications | SANL Power Circuit 60A (A+B) |
SEAT | 03.04 | rtrdcp.seat.net.internet2.edu | | DC | 35.4922 | 35.2961 | 2001 | 803 | Seattle | WA | Pacific Northwest Gigapop | SEAT (Westin) Power Circuit (#1 of 2) 100A (A+B) |
SEAT | 03.04 | rtrdcp2.seat.net.internet2.edu | | DC | 43.5114 | 43.0890 | 2001 | 803 | Seattle | WA | Pacific Northwest Gigapop | SEAT (Westin) Power Circuit (#2 of 2) 100A (A+B) |
SLAC | 1 | dwdmdcp.slac.net.internet2.edu | | DC | 17.3484 | 17.2933 | 2575 | | Stanford | CA | Energy Sciences Network | |
STAR | 0205.07 | sdn-dcp0.star.net.internet2.edu | | DC | 40.9183 | 40.4764 | 710 | 600 | Chicago | IL | Starlight Northwestern University | STAR Power Circuit 100A (A+B) |
STAR | 0205.08 | dwdmdcp.star.net.internet2.edu | | DC | 45.5834 | 46.0743 | 710 | 600 | Chicago | IL | Starlight Northwestern University | STAR Power Circuit 60A (A+B) |
SUNN | 001.001 | dwdmdcp2.sunn.net.internet2.edu | | DC | 30.0000 | 29.5825 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 60A (A+B) |
SUNN | 001.002 | dwdmdcp.sunn.net.internet2.edu | | DC | 28.8080 | 28.7749 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 60A (A+B) |
SUNN | 001.002 | obsacp.sunn.net.internet2.edu | AA | AC | 1.3101 | 1.3970 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN AC Power Circuit 20A (120V) |
SUNN | 001.002 | obsacp.sunn.net.internet2.edu | AB | AC | 0.0486 | 0.0621 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN AC Power Circuit 20A (120V) |
SUNN | 001.003 | dwdmdcp3.sunn.net.internet2.edu | | DC | 44.3988 | 44.7906 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 80A (A+B) |
SUNN | 001.004 | sdn-dcp0.sunn.net.internet2.edu | | DC | 38.9992 | 37.0121 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit (#1 of 2) 60A (A+B) |
SUNN | 001.004 | sdn-dcp2.sunn.net.internet2.edu | | DC | 38.5489 | 36.1283 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit (#2 of 2) 60A (A+B) |
Sing1 | 43c125 | acp.sing1.net.internet2.edu | AA | AC | 3.0453 | 2.4473 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c125 | acp.sing1.net.internet2.edu | AB | AC | 2.9648 | 2.3866 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c126 | acp0.sing1.net.internet2.edu | AA | AC | 1.8033 | 2.6468 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c126 | acp0.sing1.net.internet2.edu | AB | AC | 1.9270 | 2.8264 | 35 | Internet2 | Singapore | | TATA Communications | |
TUCS | 204.004 | dwdmdcp.tucs.net.internet2.edu | | DC | 24.4966 | 24.1941 | 135 | S002 | Tucson | AZ | Level(3) Communications | |
TUCS | 204.005 | sdn-dcp.tucs.net.internet2.edu | | DC | 50.9343 | 51.4310 | 135 | S002 | Tucson | AZ | Level(3) Communications | TUCS Power Circuit 80A (A+B) |
TULS | C001.0000.204.007 | dwdmdcp2.tuls.net.internet2.edu | | DC | 21.5000 | 21.3001 | 18 | | Tulsa | OK | Level(3) Communications | TULS Power Circuit 60A (A+B) |
TULS | C001.0000.204.008 | sdn-dcp.tuls.net.internet2.edu | | DC | 53.9317 | 53.3465 | 18 | | Tulsa | OK | Level(3) Communications | TULS Power Circuit 80A (A+B) |
WASH | 001.002 | obsacp.wash.net.internet2.edu | AA | AC | 3.5000 | 3.4996 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 30A (A+B) 120V |
WASH | 001.002 | obsacp.wash.net.internet2.edu | AB | AC | 3.5020 | 3.5018 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 30A (A+B) 120V |
WASH | 001.002 | rtrdcp.wash.net.internet2.edu | | DC | 44.8806 | 44.1997 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.002 | rtrdcp2.wash.net.internet2.edu | | DC | 45.8935 | 45.1736 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.003 | obsacp2.wash.net.internet2.edu | AA | AC | 2.0021 | 2.0017 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 20A (A+B) 120V |
WASH | 001.003 | obsacp2.wash.net.internet2.edu | AB | AC | 2.4999 | 2.4999 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 20A (A+B) 120V |
WASH | 001.004 | dwdmdcp2.wash.net.internet2.edu | | DC | 44.6016 | 46.2078 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.005 | dwdmdcp.wash.net.internet2.edu | | DC | 38.8625 | 45.8011 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 002.005 | dwdmdcp3.wash.net.internet2.edu | | DC | 36.5738 | 45.6275 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH2 | 001.002 | obsacp.net.wix.internet2.edu | AA | AC | 0.0000 | 0.0000 | 1755 | | McLean | VA | Level(3) Communications | |
WASH2 | 001.002 | obsacp.net.wix.internet2.edu | AB | AC | 0.0000 | 0.0000 | 1755 | | McLean | VA | Level(3) Communications | |
WILC | Rack 2 | rtrdcp.wilc.net.internet2.edu | | DC | 37.0907 | 37.5868 | 624 | | Los Angeles | CA | Wilcon or Crown Castle Fiber | WILC Power Circuit 60A (A+B) |
|