POP | Rack | Controller | Feed Name | AC|DC | Current AMPs | Avg AMPS (6 months) | Site Address Numbers | Suite Number | City | State | Facility Owner | Service |
ALBA | 001.001 | dwdmdcp.alba.net.internet2.edu | | DC | 25.4389 | 25.3783 | 194 | S002 | Albany | NY | Level(3) Communications | ALBA Power Circuit 60A (A+B) |
ALBA | 001.002 | sdn-dcp.alba.net.internet2.edu | | DC | 57.1181 | 57.8267 | 194 | S002 | Albany | NY | Level(3) Communications | ALBA Power Circuit 80A (A+B) |
ALBU | C01.004 | dwdmdcp.albu.net.internet2.edu | | DC | 45.3250 | 44.9971 | 505 | 112 | Albuquerque | NM | Level(3) Communications | ALBU Power Circuit 60A (A+B) |
ANL221 | Room 130D | dwdmdcp1.anl221.net.internet2.edu | | DC | 15.0544 | 14.9478 | 9700 | Building 221 | Lemont | IL | Energy Sciences Network | ANL221 Power Circuit ?A (A+B) |
ASHB | 202 | sdn-dcp.ashb.net.internet2.edu | | DC | 53.9067 | 53.5743 | 21715 | | Ashburn | VA | Equinix | ASHB Power Circuit 60A (A+B) |
ASHB | 210 | dwdmdcp.ashb.net.internet2.edu | | DC | 44.3827 | 47.5183 | 21715 | | Ashburn | VA | Equinix | ASHB Power Circuit 80A (A+B) |
ATLA | 001.001 | rtrdcp.atla.net.internet2.edu | | DC | 45.6376 | 46.2502 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit (1 of 2) 60 A (A+B) |
ATLA | 001.001 | rtrdcp2.atla.net.internet2.edu | | DC | 44.6978 | 45.4911 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit (2 of 2) 60 A (A+B) |
ATLA | 001.002 | obsacp.atla.net.internet2.edu | AA | AC | 3.9891 | 3.8633 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA AC Power Circuit 20A (120V) |
ATLA | 001.002 | obsacp.atla.net.internet2.edu | AB | AC | 5.7530 | 5.6666 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA AC Power Circuit 20A (120V) |
ATLA | 003.001 | dwdmdcp.atla.net.internet2.edu | | DC | 43.5441 | 43.6185 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
ATLA | 003.002 | dwdmdcp2.atla.net.internet2.edu | | DC | 43.2983 | 43.3128 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
ATLA | 003.003 | dwdmdcp3.atla.net.internet2.edu | | DC | 18.0111 | 17.8470 | 180 | S007 | Atlanta | GA | Level(3) Communications | ATLA Power Circuit 60 A (A+B) |
BALT | 001.001 | dwdmdcp.balt.net.internet2.edu | | DC | 8.9822 | 8.8803 | 300 | No Suite.
ICC | Baltimore | MD | Level(3) Communications | |
BATO | 001.001 | dwdmdcp.bato.net.internet2.edu | | DC | 25.5439 | 25.6399 | 9826 | S005 | Baton Rouge | LA | Level(3) Communications | BATO Power Circuit 60A (A+B) |
BATO | 001.002 | sdn-dcp.bato.net.internet2.edu | | DC | 49.4941 | 49.7533 | 9826 | S005 | Baton Rouge | LA | Level(3) Communications | BATO Power Circuit 60A (A+B) |
BOIS | 002.001 | dwdmdcp.bois.net.internet2.edu | | DC | 31.1007 | 30.8464 | 435 | | Boise | ID | Level(3) Communications | BOIS Power Circuit 60A (A+B) |
BOST | 001.001 | dwdmdcp.bost.net.internet2.edu | | DC | 37.4492 | 37.1513 | 300 | S002 | Boston | MA | Level(3) Communications | BOST Power Circuit 60A (A+B) |
BOST | 001.002 | sdn-dcp.bost.net.internet2.edu | | DC | 62.3167 | 62.5495 | 300 | S002 | Boston | MA | Level(3) Communications | BOST Power Circuit 80A (A+B) |
BUFF | 208.05 | dwdmdcp.buff.net.internet2.edu | | DC | 12.4903 | 12.8729 | 325 | | Buffalo | NY | Level(3) Communications | BUFF Power Circuit 60A (A+B) |
CHAR | 001.001 | dwdmdcp.char.net.internet2.edu | | DC | 40.9207 | 40.8964 | 4021 | | Charlotte | NC | Level(3) Communications | CHAR Power Circuit 60A (A+B) |
CHAR | 001.003 | sdn-dcp.char.net.internet2.edu | | DC | 50.9105 | 51.2110 | 4021 | | Charlotte | NC | Level(3) Communications | CHAR Power Circuit 80A (A+B) |
CHAT | 206.05 | dwdmdcp.chat.net.internet2.edu | | DC | 14.9616 | 14.5408 | 1601 | | Chattanooga | TN | Level(3) Communications | CHAT Power Circuit 60A (A+B) |
CHIC | 01.02 | sdn-dcp.chic.net.internet2.edu | | DC | 6.5858 | 6.6566 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.03 | dwdmdcp3.chic.net.internet2.edu | | DC | 67.6216 | 67.2906 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.04 | dwdmdcp.chic.net.internet2.edu | | DC | 40.0003 | 39.9518 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 01.05 | dwdmdcp2.chic.net.internet2.edu | | DC | 39.6852 | 39.4848 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 02.01 | obsacp.chic.net.internet2.edu | AA | AC | 7.0288 | 7.0323 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC AC Power Circuit 30A (120V) |
CHIC | 02.01 | obsacp.chic.net.internet2.edu | AB | AC | 5.5009 | 5.5007 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC AC Power Circuit 30A (120V) |
CHIC | 02.02 | rtrdcp.chic.net.internet2.edu | | DC | 39.9581 | 48.6220 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CHIC | 02.02 | rtrdcp2.chic.net.internet2.edu | | DC | 43.9662 | 43.5342 | 600 | S011 | Chicago | IL | Level(3) Communications | CHIC Power Circuit 60A (A+B) |
CINC | .01 | dwdmdcp.cinc.net.internet2.edu | | DC | 24.9992 | 24.9372 | 400 | | Cincinnati | OH | Level(3) Communications | CINC Power Circuit 60A (A+B) |
CLEV | 01.01 | dwdmdcp.clev.net.internet2.edu | | DC | 41.7419 | 41.6310 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 01.02 | dwdmdcp2.clev.net.internet2.edu | | DC | 59.8994 | 59.7830 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 75A (A+B) |
CLEV | 01.03 | rtrdcp.clev.net.internet2.edu | | DC | 39.0990 | 37.8985 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 01.03 | rtrdcp2.clev.net.internet2.edu | | DC | 42.5748 | 40.5698 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
CLEV | 03.03 | dwdmdcp3.clev.net.internet2.edu | | DC | 19.5590 | 11.5680 | 4000 | S004 | Cleveland | OH | Level(3) Communications | CLEV Power Circuit 60A (A+B) |
DALL | 001.001 | dwdmdcp.dall.net.internet2.edu | | DC | 40.0700 | 36.7920 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 60A (A+B) |
DALL | 001.002 | sdn-dcp.dall.net.internet2.edu | | DC | 73.2798 | 58.8169 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 80A (A+B) |
DALL | 001.003 | dwdmdcp2.dall.net.internet2.edu | | DC | 19.1540 | 18.6859 | 400 | 5th Floor | Dallas | TX | Level(3) Communications | DALL Power Circuit 60A (A+B) |
DENV | 001.001 | dwdmdcp.denv.net.internet2.edu | | DC | 56.5799 | 56.1177 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 75A (A+B) |
DENV | 001.002 | acp.denv.net.internet2.edu | AA | AC | 1.2829 | 1.1561 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV AC Power Circuit 20A (120v) |
DENV | 001.002 | acp.denv.net.internet2.edu | AB | AC | 0.0289 | 0.0353 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV AC Power Circuit 20A (120v) |
DENV | 001.002 | dwdmdcp2.denv.net.internet2.edu | | DC | 50.2481 | 50.6537 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 80A (A+B) |
DENV | 002.003 | sdn-dcp.denv.net.internet2.edu | | DC | 57.3228 | 59.0541 | 1850 | S002 | Denver | CO | Level(3) Communications | DENV Power Circuit 80A (A+B) |
DETR | C002.0000.005.005 | dwdmdcp.detr.net.internet2.edu | | DC | 12.5000 | 12.4959 | 19675 | | Detroit (Southfield) | MI | Level(3) Communications | DETR Power Circuit 60A (A+B) |
ELPA | 214.001 | dwdmdcp2.elpa.net.internet2.edu | | DC | 33.0859 | 33.1057 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 60A (A+B) |
ELPA | 214.002 | dwdmdcp.elpa.net.internet2.edu | | DC | 36.8185 | 37.0153 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 60A (A+B) |
ELPA | 232.001 | sdn-dcp0.elpa.net.internet2.edu | | DC | 51.5205 | 50.6057 | 501 | S004 | El Paso | TX | Level(3) Communications | ELPA Power Circuit 75A (A+B) |
EQCH | 01.01 | dwdmdcp.eqch.net.internet2.edu | | DC | 33.9738 | 33.9514 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.02 | dwdmdcp2.eqch.net.internet2.edu | | DC | 38.0397 | 37.5959 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.03 | sdn-dcp.eqch.net.internet2.edu | | DC | 39.6391 | 41.7479 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EQCH | 01.03 | sdn-dcp2.eqch.net.internet2.edu | | DC | 34.3404 | 36.2489 | 350 | 5th Floor | Chicago | IL | Equinix | EQCH Power Circuit 60A (A+B) |
EUGE | 001.007 | dwdmdcp.euge.net.internet2.edu | | DC | 37.0764 | 37.2012 | 90470 | | Eugene | OR | Level(3) Communications | EUGE Power Circuit 60A (A+B) |
FNALFCC | 1 | dwdmdcp1.fnalfcc.net.internet2.edu | | DC | 18.7559 | 18.6234 | 2 | | Batavia | IL | Energy Sciences Network | |
HART2 | C01.07 | dwdmdcp.hart2.net.internet2.edu | | DC | 20.9810 | 20.7336 | 155 | | Hartford | CT | Level(3) Communications | HART2 Power Circuit 60A (A+B) |
HART2 | C01.08 | sdn-dcp.hart2.net.internet2.edu | | DC | 37.5350 | 37.8581 | 155 | | Hartford | CT | Level(3) Communications | HART2 Power Circuit 60A (A+B) |
HOUH | 202.024 | dwdmdcp.houh.net.internet2.edu | | DC | 14.0014 | 13.9887 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 60A (A+B) |
HOUH | 202.025 | dwdmdcp2.houh.net.internet2.edu | | DC | 46.2524 | 46.0388 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 60A (A+B) |
HOUH | 202.026 | sdn-dcp.houh.net.internet2.edu | | DC | 60.8413 | 60.9952 | 1124 | | Houston | TX | Level(3) Communications | HOUH Power Circuit 80A (A+B) |
HOUS | 001.002 | dwdmdcp.hous.net.internet2.edu | | DC | 28.6679 | 28.6816 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 001.003 | dwdmdcp2.hous.net.internet2.edu | | DC | 32.9503 | 32.8475 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 001.004 | dwdmdcp3.hous.net.internet2.edu | | DC | 14.4517 | 14.3643 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.001 | rtrdcp.hous.net.internet2.edu | | DC | 21.0001 | 21.5893 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.001 | rtrdcp2.hous.net.internet2.edu | | DC | 30.6279 | 30.6197 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS Power Circuit 60A (A+B) |
HOUS | 003.002 | obsacp.hous.net.internet2.edu | AA | AC | 5.2521 | 5.2504 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS AC Power Circuit 30A (120V) |
HOUS | 003.002 | obsacp.hous.net.internet2.edu | AB | AC | 1.7500 | 1.7496 | 12001 | S023 | Houston | TX | Level(3) Communications | HOUS AC Power Circuit 30A (120V) |
INDI | 04a | dwdmdcp.indi.net.internet2.edu | | DC | 27.2207 | 27.4793 | 733 | | Indianapolis | IN | Lifeline Data Centers | INDI Power Circuit 60A (A+B) |
INDI | 06A | sdn-dcp.indi.net.internet2.edu | | DC | 57.2199 | 52.6311 | 733 | | Indianapolis | IN | Lifeline Data Centers | INDI Power Circuit 75A (A+B) |
JACK | 001.001 | dwdmdcp.jack.net.internet2.edu | | DC | 26.0000 | 25.9836 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 60A (A+B) |
JACK | 001.002 | dwdmdcp2.jack.net.internet2.edu | | DC | 5.0000 | 4.9945 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 60A (A+B) |
JACK | 001.003 | sdn-dcp3.jack.net.internet2.edu | | DC | 63.5568 | 62.7682 | 4814 | | Jacksonville | FL | Level(3) Communications | JACK Power Circuit 80A (A+B) |
JCSN | 001.001 | dwdmdcp.jcsn.net.internet2.edu | | DC | 24.0096 | 23.9967 | 111 | S001 | Jackson | MS | Level(3) Communications | JCSN Power Circuit 60A (A+B) |
JCSN | 001.003 | sdn-dcp.jcsn.net.internet2.edu | | DC | 43.8665 | 44.0397 | 111 | S001 | Jackson | MS | Level(3) Communications | JCSN Power Circuit 80A (A+B) |
JGI | Floor 1 / Room 422 | dwdmdcp.jgi.net.internet2.edu | | DC | 13.0318 | 12.9233 | 2800 | | Walnut Creek | CA | Energy Sciences Network | |
KANS | 003.001 | rtrdcp.kans.net.internet2.edu | | DC | 42.6028 | 41.7985 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
KANS | 003.001 | rtrdcp2.kans.net.internet2.edu | | DC | 42.5499 | 42.7791 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
KANS | 004.003 | dwdmdcp.kans.net.internet2.edu | | DC | 55.3762 | 50.0017 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 80A (A+B) |
KANS | 004.004 | dwdmdcp2.kans.net.internet2.edu | | DC | 42.2303 | 39.4742 | 1100 | 500 | Kansas City | MO | Level(3) Communications | KANS Power Circuit 60A (A+B) |
LACY | 410.01 | dwdmdcp.lacy.net.internet2.edu | | DC | 8.9278 | 8.9946 | 3348 | | Lacy | WA | Level(3) Communications | LACY Power Circuit 60A (A+B) |
LASV | 001.0001.C02.005 | sdn-dcp.lasv.net.internet2.edu | | DC | 49.7341 | 49.5541 | 1 | | North Las Vegas | NV | Level(3) Communications | LASV Power Circuit 60A (A+B) |
LASV | 1.03.002 | dwdmdcp.lasv.net.internet2.edu | | DC | 26.4829 | 26.4159 | 1 | | North Las Vegas | NV | Level(3) Communications | LASV Power Circuit 60A (A+B) |
LBNL | I-8 | dwdmdcp.lbnl.net.internet2.edu | | DC | 46.0016 | 46.8388 | 1 | | Berkeley | CA | Energy Sciences Network | |
LOSA | 001.001 | rtrdcp.losa.net.internet2.edu | | DC | 39.9804 | 42.6931 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 001.001 | rtrdcp2.losa.net.internet2.edu | | DC | 47.4200 | 50.0136 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 001.002 | obsacp2.losa.net.internet2.edu | AA | AC | 10.2465 | 10.1689 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 30A (120V) |
LOSA | 001.002 | obsacp2.losa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 30A (120V) |
LOSA | 001.003 | acp.losa.net.internet2.edu | AA | AC | 5.2899 | 6.5357 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA AC Power Circuit 30A (120V) |
LOSA | 001.003 | acp.losa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA AC Power Circuit 30A (120V) |
LOSA | 002.001 | dwdmdcp.losa.net.internet2.edu | | DC | 48.5452 | 48.0169 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOSA | 002.002 | dwdmdcp2.losa.net.internet2.edu | | DC | 30.9020 | 28.5709 | 818 | S002 | Los Angeles | CA | Level(3) Communications | LOSA Power Circuit 60A (A+B) |
LOUI | 001.001 | dwdmdcp.loui.net.internet2.edu | | DC | 22.2761 | 22.2586 | 848 | | Louisville | KY | Level(3) Communications | LOUI Power Circuit 60A (A+B) |
LOUI | 001.003 | sdn-dcp.loui.net.internet2.edu | | DC | 50.4295 | 52.7022 | 848 | | Louisville | KY | Level(3) Communications | LOUI Power Circuit 70A (A+B) |
MEMP | C03.011 | dwdmdcp.memp.net.internet2.edu | | DC | 21.0253 | 20.8317 | 3993 | | Memphis | TN | Level(3) Communications | MEMP Power Circuit 60A (A+B) |
MINN | 001.003 | sdn-dcp.minn.net.internet2.edu | | DC | 28.8505 | 29.0114 | 511 | | Minneapolis | MN | University of Minnesota - Twin Cities | MINN Power Circuit 70A (A+B) |
MINN | 001.003 | sdn-dcp2.minn.net.internet2.edu | | DC | 31.6669 | 31.8307 | 511 | | Minneapolis | MN | University of Minnesota - Twin Cities | MINN Power Circuit 70A (A+B) |
MISS2 | 503.101.11 | sdn-dcp.miss2.net.internet2.edu | | DC | 51.3700 | 51.0282 | 110 | 503 | Missoula | MT | iConnect Montana | |
NASH | 001.001 | dwdmdcp.nash.net.internet2.edu | | DC | 35.4699 | 35.3911 | 2990 | S009 | Nashville | TN | Level(3) Communications | NASH Power Circuit 60A (A+B) |
NASH | 001.002 | dwdmdcp2.nash.net.internet2.edu | | DC | 33.6068 | 33.5748 | 2990 | S009 | Nashville | TN | Level(3) Communications | NASH Power Circuit 60A (A+B) |
NERSC | 01 | dwdmdcp.nersc.net.internet2.edu | | DC | 30.5062 | 30.6495 | 415 | | Oakland | CA | Energy Sciences Network | |
NEWY1118TH | 001.003 | obsacp.newy1118th.net.internet2.edu | AA | AC | 0.2530 | 0.2514 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 AC Power Circuit 20A (120V) |
NEWY1118TH | 001.003 | obsacp.newy1118th.net.internet2.edu | AB | AC | 1.0000 | 0.9940 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 AC Power Circuit 20A (120V) |
NEWY1118TH | 001.004 | dwdmdcp2.newy1118th.net.internet2.edu | | DC | 37.1961 | 37.0819 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 Power Circuit 50A (A+B) |
NEWY1118TH | 001.005 | dwdmdcp.newy1118th.net.internet2.edu | | DC | 13.3663 | 20.9138 | 111 | 304 | New York | NY | Level(3) Communications | NEWY1118 Power Circuit 60A (A+B) |
NEWY32AOA | 06.07 | obsacp.newy32aoa.net.internet2.edu | AA | AC | 16.8749 | 16.8664 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit AC (TBD) |
NEWY32AOA | 06.07 | obsacp.newy32aoa.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit AC (TBD) |
NEWY32AOA | 06.08 | rtrdcp.newy32aoa.net.internet2.edu | | DC | 50.1064 | 49.9812 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 60A (A+B) |
NEWY32AOA | 06.08 | rtrdcp2.newy32aoa.net.internet2.edu | | DC | 41.0817 | 40.8283 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 60A (A+B) |
NEWY32AOA | 06.09 | dwdmdcp2.newy32aoa.net.internet2.edu | | DC | 41.9093 | 39.5598 | 32 | 24.06 | New York | NY | NYSERNet | NEWY32AOA Power Circuit 60A (A+B) |
PAIX | 0401 | rtrdcp.paix.net.internet2.edu | | DC | 30.7794 | 31.7534 | 529 | | Palo Alto | CA | Equinix | PAIX Power Circuit 60 (A+B) |
PHIL | 001.001 | dwdmdcp.phil.net.internet2.edu | | DC | 26.2579 | 26.3476 | 401 | S010 | Philadelphia | PA | Level(3) Communications | PHIL Power Circuit 60A (A+B) |
PHIL | 001.003 | sdn-dcp.phil.net.internet2.edu | | DC | 54.6811 | 56.0901 | 401 | S010 | Philadelphia | PA | Level(3) Communications | PHIL Power Circuit 80A (A+B) |
PHOE | C001.0103.001.030 | sdn-dcp.phoe.net.internet2.edu | | DC | 53.4151 | 53.3960 | 811 | | Phoenix | AZ | Level(3) Communications | PHOE Power Circuit 80A (A+B) |
PHOE | C001.0103.001.031 | dwdmdcp.phoe.net.internet2.edu | | DC | 38.4982 | 38.2882 | 811 | | Phoenix | AZ | Level(3) Communications | PHOE Power Circuit 80A (A+B) |
PITT | 001.001 | dwdmdcp.pitt.net.internet2.edu | | DC | 27.6474 | 27.6498 | 143 | S013 | Pittsburgh | PA | Level(3) Communications | PITT Power Circuit 60A (A+B) |
PITT | 001.003 | sdn-dcp.pitt.net.internet2.edu | | DC | 58.1519 | 57.8735 | 143 | S013 | Pittsburgh | PA | Level(3) Communications | PITT Power Circuit 80A (A+B) |
PORT | 001.001 | dwdmdcp.port.net.internet2.edu | | DC | 25.5181 | 25.4949 | 1335 | 011 | Portland | OR | Level(3) Communications | PORT Power Circuit 60A (A+B) |
PORT | 001.004 | sdn-dcp.port.net.internet2.edu | | DC | 63.7832 | 64.2568 | 1335 | 011 | Portland | OR | Level(3) Communications | PORT Power Circuit 80A (A+B) |
PUEB | 2.02 | dwdmdcp.pueb.net.internet2.edu | | DC | 17.7570 | 17.7209 | 211 | | Pueblo | CO | CenturyLink | |
RALE | 001.001 | dwdmdcp.rale.net.internet2.edu | | DC | 30.0001 | 29.9635 | 5301 | Dark Fiber - S007 | Raleigh | NC | Level(3) Communications | RALE Power Circuit 60 A (A+B) |
RALE | 001.003 | sdn-dcp.rale.net.internet2.edu | | DC | 60.6523 | 60.5179 | 5301 | Dark Fiber - S007 | Raleigh | NC | Level(3) Communications | RALE Power Circuit 80A (A+B) |
RENO | 210.05 | dwdmdcp.reno.net.internet2.edu | | DC | 16.6822 | 16.9999 | 220 | | Reno | NV | Level(3) Communications | RENO Power Circuit 60A (A+B) |
RENO | 216.002 | sdn-dcp.reno.net.internet2.edu | | DC | 52.6529 | 52.4262 | 220 | | Reno | NV | Level(3) Communications | RENO Power Circuit 80A (A+B) |
SACR | 001.001 | dwdmdcp.sacr.net.internet2.edu | | DC | 23.2499 | 23.1134 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SACR | 001.002 | dwdmdcp2.sacr.net.internet2.edu | | DC | 17.3970 | 17.1365 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SACR | 001.003 | dwdmdcp3.sacr.net.internet2.edu | | DC | 6.0000 | 5.9958 | 1075 | | West Sacramento | CA | Level(3) Communications | SACR Power Circuit 60A (A+B) |
SAIN | 210.002 | dwdmdcp.sain.net.internet2.edu | | DC | 11.2102 | 11.1995 | 900 | | Saint Louis | MO | Level(3) Communications | SAIN Power Circuit 60A (A+B) |
SALT | 001.001 | rtrdcp.salt.net.internet2.edu | | DC | 36.6060 | 36.9143 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.001 | rtrdcp2.salt.net.internet2.edu | | DC | 29.6830 | 30.2638 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.002 | obsacp.salt.net.internet2.edu | AA | AC | 9.9662 | 9.9837 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.002 | obsacp.salt.net.internet2.edu | AB | AC | 0.0000 | 0.0000 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.003 | dwdmdcp.salt.net.internet2.edu | | DC | 49.9957 | 49.0312 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SALT | 001.004 | dwdmdcp2.salt.net.internet2.edu | | DC | 33.2946 | 30.0202 | 572 | S007 | Salt Lake City | UT | Level(3) Communications | SALT Power Circuit 60A (A+B) |
SANA | 202.010 | dwdmdcp.sana.net.internet2.edu | | DC | 10.5000 | 10.4909 | 1203 | | San Antonio | TX | Level(3) Communications | SANA Power Circuit 60A (A+B) |
SAND | 1.003 | dwdmdcp.sand.net.internet2.edu | | DC | 8.0000 | 7.9893 | 8929 | S014 | San Diego | CA | Level(3) Communications | SAND Power Circuit 60A (A+B) |
SANL | LT01.09 cabinet rack | dwdmdcp.sanl.net.internet2.edu | | DC | 20.6794 | 20.5377 | 775 | | San Luis Obispo | CA | Level(3) Communications | SANL Power Circuit 60A (A+B) |
SEAT | 03.04 | rtrdcp.seat.net.internet2.edu | | DC | 35.4896 | 35.2725 | 2001 | 803 | Seattle | WA | Pacific Northwest Gigapop | SEAT (Westin) Power Circuit (#1 of 2) 100A (A+B) |
SEAT | 03.04 | rtrdcp2.seat.net.internet2.edu | | DC | 43.6113 | 43.0728 | 2001 | 803 | Seattle | WA | Pacific Northwest Gigapop | SEAT (Westin) Power Circuit (#2 of 2) 100A (A+B) |
SLAC | 1 | dwdmdcp.slac.net.internet2.edu | | DC | 17.3616 | 17.2926 | 2575 | | Stanford | CA | Energy Sciences Network | |
STAR | 0205.07 | sdn-dcp0.star.net.internet2.edu | | DC | 40.6594 | 40.4571 | 710 | 600 | Chicago | IL | Starlight Northwestern University | STAR Power Circuit 100A (A+B) |
STAR | 0205.08 | dwdmdcp.star.net.internet2.edu | | DC | 46.0431 | 46.0887 | 710 | 600 | Chicago | IL | Starlight Northwestern University | STAR Power Circuit 60A (A+B) |
SUNN | 001.001 | dwdmdcp2.sunn.net.internet2.edu | | DC | 30.0000 | 29.5633 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 60A (A+B) |
SUNN | 001.002 | dwdmdcp.sunn.net.internet2.edu | | DC | 28.8110 | 28.7732 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 60A (A+B) |
SUNN | 001.002 | obsacp.sunn.net.internet2.edu | AA | AC | 1.3053 | 1.4027 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN AC Power Circuit 20A (120V) |
SUNN | 001.002 | obsacp.sunn.net.internet2.edu | AB | AC | 0.0489 | 0.0628 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN AC Power Circuit 20A (120V) |
SUNN | 001.003 | dwdmdcp3.sunn.net.internet2.edu | | DC | 44.5538 | 44.5238 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit 80A (A+B) |
SUNN | 001.004 | sdn-dcp0.sunn.net.internet2.edu | | DC | 39.0116 | 36.8982 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit (#1 of 2) 60A (A+B) |
SUNN | 001.004 | sdn-dcp2.sunn.net.internet2.edu | | DC | 38.4773 | 36.0115 | 1380 | S119 | Sunnyvale | CA | Level(3) Communications | SUNN Power Circuit (#2 of 2) 60A (A+B) |
Sing1 | 43c125 | acp.sing1.net.internet2.edu | AA | AC | 3.5305 | 2.4130 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c125 | acp.sing1.net.internet2.edu | AB | AC | 3.4370 | 2.3539 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c126 | acp0.sing1.net.internet2.edu | AA | AC | 3.6347 | 2.6614 | 35 | Internet2 | Singapore | | TATA Communications | |
Sing1 | 43c126 | acp0.sing1.net.internet2.edu | AB | AC | 3.8849 | 2.8418 | 35 | Internet2 | Singapore | | TATA Communications | |
TUCS | 204.004 | dwdmdcp.tucs.net.internet2.edu | | DC | 24.4280 | 24.1807 | 135 | S002 | Tucson | AZ | Level(3) Communications | |
TUCS | 204.005 | sdn-dcp.tucs.net.internet2.edu | | DC | 50.8386 | 51.4411 | 135 | S002 | Tucson | AZ | Level(3) Communications | TUCS Power Circuit 80A (A+B) |
TULS | C001.0000.204.007 | dwdmdcp2.tuls.net.internet2.edu | | DC | 21.5044 | 21.2815 | 18 | | Tulsa | OK | Level(3) Communications | TULS Power Circuit 60A (A+B) |
TULS | C001.0000.204.008 | sdn-dcp.tuls.net.internet2.edu | | DC | 54.0082 | 53.2997 | 18 | | Tulsa | OK | Level(3) Communications | TULS Power Circuit 80A (A+B) |
WASH | 001.002 | obsacp.wash.net.internet2.edu | AA | AC | 3.5000 | 3.4995 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 30A (A+B) 120V |
WASH | 001.002 | obsacp.wash.net.internet2.edu | AB | AC | 3.5020 | 3.5017 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 30A (A+B) 120V |
WASH | 001.002 | rtrdcp.wash.net.internet2.edu | | DC | 44.8806 | 44.1026 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.002 | rtrdcp2.wash.net.internet2.edu | | DC | 45.8935 | 45.0612 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.003 | obsacp2.wash.net.internet2.edu | AA | AC | 2.0021 | 2.0017 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 20A (A+B) 120V |
WASH | 001.003 | obsacp2.wash.net.internet2.edu | AB | AC | 2.4999 | 2.4999 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH AC Power Circuit 20A (A+B) 120V |
WASH | 001.004 | dwdmdcp2.wash.net.internet2.edu | | DC | 44.6477 | 46.4609 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 001.005 | dwdmdcp.wash.net.internet2.edu | | DC | 46.2497 | 45.7675 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH | 002.005 | dwdmdcp3.wash.net.internet2.edu | | DC | 43.6886 | 45.8498 | 1755 | 022 | McLean | VA | Level(3) Communications | WASH Power Circuit 60A (A+B) |
WASH2 | 001.002 | obsacp.net.wix.internet2.edu | AA | AC | 0.0000 | 0.0000 | 1755 | | McLean | VA | Level(3) Communications | |
WASH2 | 001.002 | obsacp.net.wix.internet2.edu | AB | AC | 0.0000 | 0.0000 | 1755 | | McLean | VA | Level(3) Communications | |
WILC | Rack 2 | rtrdcp.wilc.net.internet2.edu | | DC | 36.5953 | 37.6004 | 624 | | Los Angeles | CA | Wilcon or Crown Castle Fiber | WILC Power Circuit 60A (A+B) |
|